招标
【设备类】中国电建水电一局埃塞AGRO工业园3A/4A项目交直流电源采购项目询价公告
金额
-
项目地址
吉林省
发布时间
2021/09/01
公告摘要
项目编号powerchina-0101006/016-21094
预算金额-
招标联系人苗利宝
标书截止时间-
投标截止时间-
公告正文

【设备类】中国电建水电一局埃塞AGRO工业园3A/4A项目交直流电源采购项目询价公告

来源:设备物资集中采购电子平台 作者:设备物资集中采购电子平台:苗利宝 发布时间: 2021-09-01
询 价 函

招标编号:POWERCHINA-0101006/016-21094

中国水利水电第一工程局有限公司

埃塞俄比亚AGRO工业园输变电

项目交直流蓄电池采购项目

询价公告

中国水利水电第一工程局有限公司

二〇二一年八月

中国·长春

询价公告

一、投标邀请书

中国水利水电第一工程局有限公司拟对埃塞俄比亚AGRO工业园输变电项目所需要现拟采购交直流蓄电池进行线上公开询价采购,请贵公司收到询价函后根据要求进行报价。

1、工程简介

项目中文名称:埃塞俄比亚ARGO工业园输变电项目

项目英文名称:Procurement of Design, Manufacture, Test, Supply ,Erection and commissioning of

LOT-3A: Design, Manufacture, Test, Supply, Erection and Commissioning of 132kv Substation for Ganda Arba Agro Industry Park Power Transmission Project.

LOT-4A: Design, Manufacture, Test, Supply, Erection and Commissioning of 132 kv substation for Weynenta Agro Industry Park Power Transmission Project.

实施范围:

新建132kV Ganda变电站设备材料供货,包括2个132kV变压器间隔,2个132kV线路间隔和1个132kV母联间隔。

升级改造132kV Shasemene变电站设备材料供货,

升级改造132kV Adamitulu变电站设备材料供货

新建132kV Weynenta变电站设备材料供货,包括2个132kV变压器间隔,1个132kV线路间隔和1个132kV母联间隔。

升级改造132kV Yirgalem-II 变电站设备材料供货, 包括1个132kV线路间隔。

合同工期:12个月

三、响应文件的递交

本次采用中国电建集采平台进行询价,报名截止时间2021年9月4日15:00时。该报价单作为后续合同谈判的主要依据,上述报价资料(报价单、设备详细参数及配置等)请在2021年9月7日北京时间15:00时前上传至集采平台(http://ec.powerchina.cn/)。在线填报金额必须与附件报价单一致,逾期系统将不予受理。

四、报价要求:

1、含到上海港或天津港的车板交货价、含13%全额增值税专用发票、包装费、国内运输费、保险费、商检费等。

2、质保期:质保期自货物到达国内指定港口交货后24个月。

3、请注明交货期。

4、报价有效期为90天。

5、上传报价时请提供PDF版和可编辑版。

6、本批次采购交货地点分为天津港或上海港。

7、报价时需提供检验报告。

8、要求提供海外同产品业绩10项以上,并附业绩证明材料。

五、联系方式

采 购 人:中国水利水电第一工程局有限公司

地??? 址:吉林省长春市经开区东南湖大路3799号

邮??? 编:130000

公司联系人:苗利宝(电话:0431-87974974)

国际公司联系人:冯茜(电话:18137829104)

2021年8月31日

需求一览表:

序号

名称

主要参数

单位

数量

交货日期

交货地点

备注

AC AUXILIARY SERVICE SUPPLY

1

UPS (uninterruptible power supply)

10kVA

100Ah

No.

1

Ganda

2

Set of 380V, AC auxiliary service board complete with all necessary equipment

Lot

1

Ganda

DC AUXILIARY SERVICE SUPPLY

1

Station Battery 125 V complete with? all accessories (60+4 cells), a minumum of 500 Ah

500Ah

Set

2

Ganda

2

125V DC, Station Battery charger, 210A,

No.

2

Ganda

3

Set of 125V DC auxiliary service distribution board complete with all equipment/accessories

Lot

1

Ganda

4

Station Battery (lead acid type)? 48 V, twenty four (24) cells and two (2) spare cells complete with? all accessories for? Communication equipmen. The minimum rating of each cell shall be of 250Ah for 10hours with double pole fuse box complete with HRC fuse.

250Ah

Set

1

Ganda

5

48V DC, station battery charger

No.

2

Ganda

6

Set of 48V DC distribution panel

Lot

1

Ganda

DC AUXILIARY SERVICE SUPPLY MODIFICATION

1

Station Battery (lead acid type)? 48 V, twenty four (24) cells and two (2) spare cells complete with? all accessories for? Communication equipmen. The minimum rating of each cell shall be of 250Ah for 10hours with double pole fuse box complete with HRC fuse.

Set

1

Shasemene

2

48V DC, station battery charger

No.

2

Shasemene

3

Set of 48V DC distribution panel

Lot

1

Shasemene

DC AUXILIARY SERVICE SUPPLY MODIFICATION

1

Station Battery (lead acid type)? 48 V, twenty four (24) cells and two (2) spare cells complete with? all accessories for? Communication equipmen. The minimum rating of each cell shall be of 250Ah for 10hours with double pole fuse box complete with HRC fuse.

Set

1

Adamitulu

2

48V DC, station battery charger

No.

2

Adamitulu

3

Set of 48V DC distribution panel

Lot

1

Adamitulu

AC AUXILIARY SERVICE SUPPLY

1

UPS (uninterruptible power supply)

10kVA

100Ah

No.

1

Weynenta

2

Set of 380V, AC auxiliary service board complete with all necessary equipment

Lot

1

Weynenta

DC AUXILIARY SERVICE SUPPLY

1

Station Battery 125 V complete with? all accessories (60+4 cells), 400 Ah

400Ah

Set

2

Weynenta

2

Battery charger, 125 V DC, 160 A, DC

No.

2

Weynenta

3

Set of 125V DC auxiliary service distribution board complete with all equipment/accessories

Lot

1

Weynenta

4

Station Battery (lead acid type)? 48 V, twenty four (24) cells and two (2) spare cells complete with? all accessories for? Communication equipmen. The minimum rating of each cell shall be of 250Ah for 10hours with double pole fuse box complete with HRC fuse.

250Ah

Set

1

Weynenta

5

48V DC, station battery charger

No.

2

Weynenta

6

Set of 48V DC distribution panel

Lot

1

Weynenta

备件:

序号

名称

主要参数

单位

数量

交货日期

交货地点

备注

125 V and 48 V, DC supply system

1

MCB's for each type used on 125 V, DC system

Each

1

Ganda

2

MCB's for each type used on 48 V, DC system

Each

1

Ganda

3

Diodes of each type and rating used

Each

1

Ganda

AC auxiliary supply system

1

MCB's for each type used

Each

1

Ganda

2

Fuses for each type used

Each

1

Ganda

3

Auxiliary Relays of each type used

Each

1

Ganda

125 V and 48 V, DC supply system

1

MCB's for each type used on 125 V, DC system

Each

1

Weynenta

2

MCB's for each type used on 48 V, DC system

Each

1

Weynenta

3

Diodes of each type and rating used

Each

1

Weynenta

AC auxiliary supply system

1

MCB's for each type used

Each

1

Weynenta

2

Fuses for each type used

Each

1

Weynenta

3

Auxiliary Relays of each type used

Each

1

Weynenta


技术规范

B1.3.10 AUXILIARY SERVICE SUPPLY

I) 380 V, AC LOW VOLTAGE SYSTEM

Set of 380 V, AC distribution panels/boards shall be provided. The final number of distribution boards to be determined by the Contractor but the minimum shall be:

Non-Essential loads

Essential Loads

Incoming lines boards

The distribution switchboards shall have three-phase, four-wire, complete with 3-phase and neutral bus bars (essential and non-essential) and all necessary ancillary equipment including:

a) 3-phase circuit breaker, motor operated suitable for the connection of incoming power cables from the 33 kV auxiliary transformers. The circuit breakers shall be motor operated (Closing and Opening electrically) and interlocked with the incoming feeder from the stand-by diesel generator.

b) 3-phase circuit breaker, motor operated suitable for the connection of incoming power cables from the diesel generator. The circuit breakers shall be motor operated (Closing and Opening electrically) and interlocked with the incoming feeder from the 33 kV auxiliary transformer.

c) 4-pole MCB complete with thermal overload tripping device for the outgoing feeders. The Contractor during detail design shall determine number of feeders (essential and non-essential) and current rating.

d) Two 380 V, bus bars with flat copper dimension as required and one earth bar (one bus bar for essential loads and one for non-essential loads);

e) Two voltmeters scaled 0-500 volts having 72 x 72 mm dial, 240o movement, with phase selector switch (one voltmeter for essential bus and one for non-essential bus);

f) One ammeter scaled 0-500 A having 72x72 mm dial, 240o movement, with phase selector switch for each incoming feeder (for 0.4 kV incoming from 33/0.4 kV auxiliary transformer).

g) One numerical type energy meter (kWh and KVArh) for each incoming feeder (for 0.4 kV incoming from 33/0.4 kV auxiliary transformer).

h) Toroidal type current transformer for instrumentation of each incoming;

i) A manual / off / automatic switch;

On manual the lighting shall be switched by on/off push button or switch.

On Off the lighting shall be switched off.

On Automatic the lighting shall normally be operated by a photocell.

j) One voltage failure relay to cover failure of any phase on the distribution switchboard to initiate supply failure contacts for local, remote and supervisory indication;

k) Over current and earth fault relay to trip each incoming 380 V circuit breaker

l) Current transformer for instrumentation and protection quantity and ratio as required

n) The necessary number of sub distribution MCBs boards (essential and non-essential) adequate for the purposes specified under this contract shall be included in this Contract. Including, spares of each size of MCBs unit used shall be incorporated and wired on the board;

o) Provision shall be made for the following supplies:

Switchyard outside security lighting

Protection and auxiliary supplies building lighting

3-phase power socket panel

Light sensitive switch

All necessary operation, instruction and warning labels shall be provided including 3-phase 4 wires, switchgear mounted for oil treatment plant etc.

p) Lighting and small power distribution and sub-distribution boards of the recessed type finished flush with the walls where recessed conduit is used normally located in the LV, AC room. Other locations shall be agreed with the Engineer.

B1.3.11. BATTERIES, CHARGERS AND DC DISTRIBUTION EQUIPMENT

I) 125V DC STATION BATTERIES

Two (2) complete sets of lead acid batteries suitable for substation application of the high performance, minimal maintenance free type each complete with stands, connections, connection facilities, output fuses etc.

The capacity of each battery to be capable of supporting the protection Control, alarm and indications load for a 12 hour period following failure of the charges or A.C supply. The number of individual cells for 125V system shall be sixty (60), four (4) cells shall be spare and rated with a minimum of 500 Ampere-hour. The final rating shall be decided after battery size calculation approved by the engineer. Each battery shall be supplied with double pole fuse box complete with HRC fuse.

Two (2) battery sets mounted on separate rack shall be provided for the 125 V DC supply system.

II) 125V, DC STATION BATTERY CHARGERS

Two (1+1) identical chargers shall be provided for the 125 Volt DC lead acid battery and Station Load. In normal operation mode, each charger shall be permanently connected across the battery and its load, for operation in float and equalization modes. The chargers shall independently be capable of supplying power to the load with the battery disconnected. The chargers shall be rated such that charger can independently supply full load plus spare capacity.

Each charger shall be contained in ventilated steel cubicle, mounted adjacent to its DC distribution panel to form a panel of matching and appearance. The batteries, chargers and DC switchboards shall conform to the requirements of this Section and where applicable, the other Sections of this Specification with regard to fuses, miniature circuit breakers (MCB), small wiring, instruments, earthing, switchboards, isolators, cubicles, etc.

The chargers shall comprise be mounted on sheet steel floor mounted cubicle complete with all controls, relay equipment, charge ammeters, voltmeters, float/boost indicators, boost charge, warning lamps and full alarms etc.

The chargers shall be fitted with output filters for limiting the output ripple when supplying standing load. The charger shall be suitable for connection to a 380 V, 3 phase, 50 Hz input supply voltage and its output shall be 210 A, DC.

III) 125V, DC DISTRIBUTION PANEL

Set of distribution boards, comprising sheet steel wall mounted cubicles complete with all necessary total charge ammeters, battery discharge ammeter with high/low sensitivity switch, voltmeters, boost charge, warning lamps, charge fail and earth fault relays, voltage sensitive relays together with all indications and alarms.

IV) 48V, DC BATTERY FOR COMMUNICATION EQUIPMENT

One (1) complete sets of lead acid batteries suitable for substation application of the high performance, maintenance free type each complete with cubicle, stands, connections facilities, output fuses etc.

The capacity of the battery system is to be capable of supporting the complete communication equipment 48 V, D.C load for a8-hour period following failure of the charges or A.C supply. The number of individual cells for 48 V system shall be twenty six (26), two (2) cells shall be spare and rated each cell shall deliver 250 Ampere hours for a 10 hours/period.

Two (2) battery sets mounted on separate rack shall be provided for the -48 V DC supply system.

V) 48V, DC BATTERY CHARGER

Two identical chargers shall be provided for the 48 Volt DC lead acid battery and Station Load. In normal operation mode, one of the chargers shall be permanently connected across one battery and its load, and the other charger shall be permanently connected across the other battery and its load, all for operation in float and equalization modes, they're independent of each other.. The rated capacity of every charger should be able to meet the requirements of charging the entire load and charging the corresponding battery unit at the same timerectifier module should be N + 1 redundant configuration. The communication equipment has dual - 48V power supply, and any charger failure will not affect the power supply and normal operation of communication equipment.

Every charger shall receive supply from two separate 380 V, AC bus bar. Any one of AC power failure will not affect the normal operation of the charger.

The chargers shall be fitted with output filters for limiting the output ripple when supplying standing load. The charger shall be suitable for connection to a 380 V, 3 phase, 50 Hz input supply voltage.

VI) 48V, DC DISTRIBUTION PANEL

Set of distribution boards comprising sheet steel flour mounted cubicles complete with all necessary to the charge ammeters, battery discharge ammeters with /low sensitivity, switch voltmeters, boast charge, wiring lamps, charge fall with all indications and alarms.

B2.1? BATTERY, CHARGERS AND DISTRIBUTION PANELS

B2.20.1 BATTERIES AND CHARGERS

B2.20.1.1 General

The Battery shall be located in a separate battery room.

Dual chargers shall be provided for each protection and control batteries system? and for the 48 V System required for the telecommunication system.

The batteries, chargers and DC switchboards shall conform to the requirements of this Section and where applicable, the other Sections of this Specification with regard to fuses, miniature circuit breakers (MCB), small wiring, instruments, earthing, switchboards, isolators, cubicles, etc.

B2.20.1.2 Battery Type

Lead acid batteries shall be one block for one cell type (single cell in plastic container type) suitable for substation application and shall be rated to give the required capacity under site environmental conditions. Sealed type batteries or more than one cell in one plastic container are not acceptable.

B2.20.1.3 Batteries

Cell boxes shall be manufactured from annealed glass or an approved clear plastic of ample strength. Sufficient space shall be provided beneath the plates to accommodate any deposit, which may accumulate at the bottom of the cell without short-circuiting the plates. The life of the cell shall not be limited by the accumulation of deposit.

Each cell shall be supplied in one block container of moulded plastic or synthetic rubber with venting plugs for topping up and measurement of electrolytic level specific gravity and temperature. The supply shall include a complete mounting rack, all inter-cell connectors needed for complete assembly of a battery, lugs for interconnecting battery sections and for connecting the whole battery to the charger and cells.

The Contractor shall provide the manufactures instructions for the charging batteries. The re­quired sulphuric acid for the initial filling of the battery shall be supplied separately in suitable containers and the quantity of sulphuric acid supplied shall be 20% in excess of what is required for the initial filling.

The batteries are to be mounted on insulators carried on wooden stands and shall be arranged in single rows of single or double tiers.? Stands shall be treated with two coats of acid resisting enamel of approved colour, and arranged so that the bottom of the battery shall not less than 300 mm above the floor.

Separators shall be provided between plates to prevent metallic conduction whilst permitting electrolyte conduction.? Separators shall be suitable for continuous immersion in the electrolyte without distortion.

Battery cells shall be clearly identified by numbering.

The number of individual cells for the 125 system shall be sixty (60), each cell shall deliver the Ampere hours specified in Part B-1 “scope of Supply” for each substation for 12 hours with its terminal voltage not falling below 1.9 volts. The 56 cells will be used for the system and the rest four (4) cells shall be spares.

The number of individual cells for the 220 Volts system shall be hundred four (104), each cell shall deliver the Ampere hours specified in Part B-1 “scope of Supply” for each substation for 12 hours with its terminal voltage not falling below 1.9 volts. The 100 cells will be used for the system and the rest four (4) cells shall be spares.

The number of individual cells for the 48 volts system shall be twenty-six (26), each cell shall deliver the Ampere hours specified in Part B-1 “scope of Supply” for each substation for 12 hours with its terminal voltage not falling below 1.9 volts.? The 24 cell will be used for the system and the rest two (2) cells shall be spares.

B2.20.1.4 Copper Connections

The copper connections between rows of cells and from the battery to the through wall bushings where applicable, shall be supplied, and be of annealed copper rod of adequate cross section, supported on insulators of an approved type. This copper rod shall be insulated by PVC or other approved taping or sleeving. All necessary-fixing arrangements shall be provided.

B2.20.1.5 Accessories

Each battery (the 220, 125 V and 48V) shall be provided with the following appropriate accessories:

? One (1) cell testing voltmeter equipment including voltmeter and thermometer.

? Two (1) syringe hydrometers, of suitable scale

? One (1) plastic filler bottle for distilled water.

? One (1) cell bridging connector.

? One (1) instruction card and record chart.

The following spare parts shall be provided:

? Three (3) vent hole type thermometers;

? Two (2) connectors bolt wrenches;

? Inter-cell connectors;

? Five (5) vent plugs;

? Five (5) connector bolts;

? Five (5) seal rings;

? One (1) lifting device for cells;

? One (1) kg of acid-resisting paint for racks; and

? Sealing compound sufficient for the battery.

? Electrolyte of normal gravity equal in volume to 10% of the electrolyte in the battery, but not less than 1 liter.? This shall be delivered in unbreakable red containers with screwed stoppers appropriately labelled.

B2.20.1.6 Battery Chargers

The charger shall be contained within a floor-mounting or wall-mounting, self ventilated cabinet, sheet steel enclosure having a hinged front cover with locking facilities, giving full access to all components and cable connections. All controls shall be placed inside. Where ventilation openings are provided, these shall be fitted with drip-proof louvers and fine mesh wire or perforated screens to exclude small insects and vermin.

Static rectifier type chargers are required. The chargers shall be of the automatic, self-regulating silicon type rectifier, unfiltered type, and shall be suita­ble for connection to a 380 volts, 3-phase, 50 Hz power supply with ?10 % line voltage variation at normal float voltage setting.

Equipment shall be housed in a floor-mounted, free-standing, self-supporting, self-ventilated cabinet with instruments and controls arranged on a front panel.? Access to the inside shall be by hinged doors or removable panels. The cabinet shall be suitable for conduit entrance from the top and bottom. Exterior surfaces shall be finished with a light grey paint.

Factory tests shall be made in accordance with the pertinent requirements of the regulatory bodies and applicable stan­dards.? No special tests are required.

An override selector switch shall be provided inside the charger unit to enable a first conditioning charge to be made, in line with the battery manufacturer’s recommendations, for batteries, which are shipped dry and require forming at site.

Chargers shall be self-protecting in the event of continuous overload and shall be suitable for re-adjustment to correct for the ageing of rectifiers and other parts.

Each charger shall be of the automatic constant voltage type arranged to float charge the battery at just below gassing level.? For this purpose it shall be arranged with a constant voltage charge range adjustable from approximately 2.15 volts up to 2.35 volts per cell, by continuous adjustment.? The float charger maximum current rating shall be sufficient to meet the total standing load current on the DC distribution board plus a battery charging current in amperes, equal numerically to 7% of the battery capacity at the 10 hour rate.

The charger shall have also a taper characteristic boost charging facility which shall be selectable by a float/boost charge selection switch and which will give boost charging up to 2.6 volts per cell.

Smoothing capacitors in the output circuit shall be provided such that the battery charger can still operate and supply the substation standing load with the battery disconnected.

B2.20.1.7 Duty of Chargers

The chargers will under normal operation be used for supplying a floating voltage, the charger shall maintain that voltage within close limits and automatically adapt to continuous and fluctuating loads within their capacity, simultaneously charg­ing at the proper rate.? The charger shall be designed with a performance on float charge such that, with the output voltage set at approximately 2.25 volts per cell, at 50% load and rated input voltage and frequency, the output voltage shall not vary by more than +1% to - 1% with any combination of input supply voltage and frequency variations as stipulated under this Specification and output current variation from 0-100%.

Voltage regulating equipment (diodes or similar) shall not be in service during float charge, but only during boost charge operation.

The charger shall be designed with a performance on boost charge such that, with rated input voltage and frequency the charger output shall not be less than its rating in watts at 2.0 and 2.6 volts per cell and also over the rating range 0-100% the output voltage shall be 2.5 to 2.6 volts per cell.

The charger shall be of 100% capacity and suitable for operating alone.

The chargers shall have reverse-current protection to prevent draining the battery in the event of rectifier failure or short circuit.

Each charger (48 V, 125 V and 220 V chargers) shall include the following equipment:

? Input voltmeter and ammeter (AC), 72x 72mm, 240? movement

? Output DC voltmeter and ammeter (load side), 72x72 mm, 240? movement

? Output DC voltmeter and ammeter (battery side), 72x72 mm, 240? movement

? Set of three-pole circuit breaker and/or contactor for AC input with overload protection.

? Set circuit breaker with overcurrent protection for DC output.

? Selector switch for “Float” or “Boost”.

? Indication lamps for “float” and “equalize” charging

? Equalize charge timer with a range of 0-24 hr.

? Indicating lamps for AC supply “On” and “equalizing charge”.

? Charger fail relay to operate within 30 seconds of the charging current failure with contacts for the local indicating lamp, remote and supervisory alarms.

? Charger supply fail relay with contacts for the local indicating lamp, remote and supervisory alarms.

? State of charge of battery indicator.

? Battery earth alarm.

? A lamp/LED indicating that a module is in service.

? A lamp/LED indicating that a module is on boost charge.

? A lamp/LED indicating that a module is faulty.

? A lamp/LED indicating that charger MCB or fuse failure /trip.

? A lamp/LED indicating that charger output over-voltage.

? Test push-button for checking all lamps/LEDs.

? Peak pulse limiter zener type.

? Input and output protection and isolation MCBs for the modules and the charger as a whole.

B2.20.1.8 Boost Charge Disconnection

An adjustable automatic device shall be supplied to disconnect the boost charge after a period adjustable between 0-2 hours.

B2.20.1.9 Transformers

Each charger shall be completed with three phase (3 x 380, V, AC primary voltage) transformer of suitable rating and connection design for the specified auxiliary supply voltage.? Off-circuit tapping shall be provided on the primary windings and the change of tapping shall be by means of links situated in an accessible position. The transformer shall be capable of carrying the specified continuous output on all tapping.

B2.20.1.10 Rectifiers

All rectifiers and semi-conducting devices employed in the charger shall be of the silicon type.? They shall be adequately rated with due regard to the air temperature within the charger enclosure for the maximum ambient temperature.

B2.20.1.11 Battery Earthing and Earth Fault Indication

The positive pole of 48-volt batteries shall be solidly earthed.

125 V and 220 V (nominal) batteries shall operate unearthed.? Means shall be provided to detect low insulation resistance of all the wiring connected to the battery by the following method and to give an earth fault alarm.

The earth fault detection circuit shall consist in principle of a resistance connected across the battery output on the distribution side of the fuses with a relay connected between the centre point of this resistance and the earth terminal.? Any unbalanced leakage current due to the low insulation resistance of the wiring connected to either pole of the battery shall cause a current to flow in the relay, which will operate at the predetermined value.

The earth fault relay shall be equipped with a minimum of two normally open contacts for local indication and remote alarm circuits.

The DC system shall be fitted with monitoring devices to check the continuity of the battery circuit.? In particular an alarm shall be provided if a battery fuse fails or if the battery circuit impedance rises above a predetermined level due to poor intercell connection or whatever.? At least two sets at voltage free contacts shall be provided for use with remote and supervisory alarm schemes.

B2.20.1.12 “Charger Fail” Indication

An approved charger fail relay shall be provided for each charger to detect failure of the DC output of the low-rate charger and also fall of battery volts below the low-rate value. These relays shall operate an indicating lamp on the DC distribution switchboard and shall have additional contacts for operating a remote alarm.? This alarm shall be immune from normal surges.? The alarm shall not be initiated when any one charger is switched off.

B2.20.1.13 Fuse Box

Each battery shall be supplied with a double pole fuse box complete with HRC fuses. The fuses shall be installed in the connections between the battery and charger.? The rating of the above fuses shall be such that they will discriminate clearly with the largest DC fuse or miniature circuit breaker used in the distribution circuits.

B2.20.1.14 Data for chargers

a) Common for all chargers (220 V DC, 125 V, DC and 48 V, DC)

- Supply voltage 400 V ± 10% three-phase

- Supply frequency 50 Hz ± 5%

- AC supply short circuit current for sizing equipment 24 kA / 1 s

- Test voltage at industrial frequency

a) AC side 2 500 V

b) DC side 2 000 V

- Battery Charger current limit (set up value) from 20 % to 50% of rated current

- output current

- Regulation accuracy

a) in voltage 1 %

b) in current 1 %

- Dynamic voltage tolerance with instantaneous

- 50 % load change

a) voltage tolerance ± 5 %

b) transient recovery time 0.5 s

- Ripple factor less than 5%

- Noise level admitted 50 dB(A)

- AC auxiliary voltage 230 V - 50 hz

- Short circuit current for 230 V AC 24 kA

- Minimum protection class IP 41

- Cooling Natural air ventilation

b) 125, V DC Charger Data

- Continuous rated current not less than 60 A, DC

- Adjustable range of output voltage:

a) floating operation 110 - 125 V

b) automatic charge operation 110 - 130 V

c) manual charge operation 110 - 150 V

- DC short circuit current for sizing equipment 12 kA / 1 s

c) 220, V DC Charger Data

- Continuous rated current not less than 60 A, DC

- Adjustable range of output voltage:

a) floating operation 195 - 220 V

b) automatic charge operation 195 - 230 V

c) manual charge operation 195 - 265 V

- DC short circuit current for sizing equipment 12 kA / 1 s

d) 48, V DC Charger Data

- Continuous rated current not less than 50 A, DC

- Adjustable range of output voltage:

a) floating operation 48 - 55 V

b) automatic charge operation 50 - 58 V

c) manual charge operation 48 - 65 V

- DC short circuit current for sizing equipment 6 kA / 1 s

B2.20.2 DC DISTRIBUTION PANELS

B2.20.2.1 General

The DC distribution panels/cubicles shall be mounted in metal sheet cubicles.

The DC switchboards shall conform to the requirements of this Section and where applicable, the other Sections of this Specification with regard to fuses, miniature circuit breakers (MCB), small wiring, instruments, earthing, switchboards, isolators, cubicles, etc.

B2.20.2.2 DC Control and Distribution panel

The DC distribution board shall house all equipment necessary for the distribution of the station DC circuits; they shall be at least of protection class IP42 to IEC 144 with self-cooling. Outgoing feeder cables shall enter from the bottom and cables and cable lugs shall be provided to the material described above.

The switchgear shall be in accordance with relevant clauses of the Specification incorporating miniature circuit breakers (MCB) units of quick-break type which shall be suitable for carrying continuously the rated current and of making or breaking this current.? Where a link- switch is specified an assembly similar to the fuse-switch shall be supplied, but the fuses shall be replaced by bolted copper links.

The equipment shall be capable of carrying, making and breaking the maximum possible fault current and details of the make-up of this shall be provided.? Curves of battery current plotted against time under short-circuit conditions shall be supplied.

Outgoing distribution cables shall be connected directly to the relevant fuse and/or link, or circuit breaker.

Cabling and wiring termination shall be shrouded to avoid accidental short-circuit or earthing of the battery.? PVC insulation shall be used for fuse wiring connections.

Means shall be provided, to limit the voltage at the outgoing terminals of the distribution board to a value not greater than the lowest continuous maximum voltage rating of the relays, instruments etc., connected to it.? The scheme, which may incorporate counter cells or back-off diodes, shall function particularly during boost charging.

DC PANEL

? One miniature circuit breaker appropriately dimensioned for battery protection.

? One miniature circuit breaker appropriately dimensioned for charger protection

? Other miniature circuit breakers (for all outgoing line feeders and 30% spare feeders fully equipped with MCB), quantity and current ratings as required.

? One ammeter, 72x72 mm, 240? movements, appropriately scaled, to measure total DC load of the distribution board.

? Battery charge/discharge current ammeter (0 - 200% normal standing load) 72x72 mm, 240? movements.

? One ammeter, 72x72 mm, 240? movements, appropriately scaled, to measure charger output.

? One output voltmeter (0 - 120% max. rated output).

? One DC insulation level testing device.

? One DC earth fault indication (supervision) relay.

? Push buttons or switches to test or switch ON/OFF the DC emergency lighting system (only for 125 Volt system).

? One under voltage relay complete with annunciation table.

? AC/DC contactors, which shall operate immediately upon cessation of an AC, supply to connect and supply the DC emergency lighting system (only for 125 Volt system).

? One manual/off/automatic selector switch for emergency DC lighting control system.

? All required bus appropriately dimensioned.

? Terminal blocks as required.

? Mimic bus.

? Labels.

B2.1 LIGHTING AND LOW VOLTAGE POWER SERVICES

B2.21.1 General

One auxiliary service board consisting of several panels for alternating current (AC) auxiliary services shall be supplied. The construction of the panels of the auxiliary service boards shall be similar, as far as practicable, to that of the panels of the control board.

Metal-clad outdoor distribution boxes for AC branch circuits shall be supplied complete with equipment as specified herein and other devices as required. The supply shall include galvanized steel support frames.

The AC low voltage circuit breakers shall have current ratings as required, and shall be supplied with short-circuit and thermal releases. They shall be of high quality air-break type, rated for 500 volts for 3-phase and 380 volts for single phase.

B2.21.2 Equipment Details

The following tabulations of equipment and devices include only the major items to be installed in the panels of the auxiliary services boards and metal-clad distribution boxes, and do not necessarily include all other required items, which are also to be supplied and installed.

B2.21.3 AC DISTRIBUTION PANEL

A complete 380 volts three-phase, four-wire AC distribution panel which shall comprise of a steel standing, front access metal enclosure complete with 600 ampere three-phase and neutral bus bars and all necessary ancillary equipment including: -

? two (2) three pole motor/solenoid operated circuit breakers for incoming feeders (one C.B to be connected to low voltage side of auxiliary transformer cable and one C.B to be connected to low voltage side of standby diesel generator cable)

? 4-pole MCBs complete with thermal overload tripping device, quantity and current rating as required for the outgoing feeders.? The number of feeders and ratings shall be determined by the Contractor during detail design stage.

? One voltmeter scaled 0-500 volts having 72x72 mm dial, 240? movement, with phase selector switch for seven positions

? One ammeter scaled 0-500 A having 72x72 mm dial with phase selector switch.

? Bus bar system with flat copper, dimensioned as required.

? One manual / off / automatic selector switch for switchyard lighting control system.

? One earth bar.

? Push buttons for switchyard lighting on/off control.

? Current transformers for instrumentation and protection, 500 V, quantity and transformation ratio as required.

? Photocell control circuit for switchyard lighting.

? One three-phase KWhr meter.

? Push buttons for the incoming feeder circuit breaker on/off operation.

? Mimic bus, labels

? One voltage failure relay to cover failure of any phase on the distribution switchboard to initiate supply failure contacts for local, remote and supervisory indication.

? Indicating lamps (quantity as required).

? A minimum of 30% spare feeders, fully equipped with each type of MCB unit and terminal blocks shall be fitted on the panel for future extension work use.

? The necessary number of distribution boards adequate for the purposes specified under this Contract shall be supplied in this Contract. Including, a minimum of 30% spares of each size of MCB unit and terminal blocks used shall be incorporated on the board.

Provision shall be made for the following supplies:

? Switchyard outside security lighting;

? Protection and Aux. Supplies control Building lighting (control room lighting);

? 3-phase and single phase power sockets in control room (where required) and terminal cabinets;

? Light Sensitive switch;

? All necessary operation, instruction and warning shall be provided;

? One 3-phase, 4 wires, 250 Amp plug mounted on a separate structure for oil treatment plant shall be provided in the immediate vicinity of associated power transformers for oil treatment plants.

B2.21.4 System of Installation

The installation shall comply with current IEC Wiring Regulations for Electrical Installation.

All fuse switchgears, distribution panels, circuit-breakers, fuses, contactors, cables and earthing systems, provided for these services shall be consistent with the design and manufacture of similar equipment detailed under relevant clauses in this Specification.

The supply of these services shall be distributed through distribution boards fitted with HRC fuses or miniature circuit- breakers.? All distribution boards shall have spare circuit and in addition shall have spare ways and due allowance made for extension facilities indicated.

System wiring shall generally be PVC insulated cables with copper conductors in continuous conduit.

Security and roadway lighting cables shall be copper conductors, PVC insulated; PVC sheathed, steel wire armoured and PVC sheathed overall.

B2.19.3.6 Uninterruptible Power Supply (UPS)

a. Operating Characteristics

For the safe supply of the servers, operator and engineering work stations and other equipment requiring continuous supply a UPS shall be provided with the following characteristics:

? Rated Output 10 kVA

? Supply Voltage 125 V DC & 110VDC

? Output Voltage 220/230/240 Selectable

? Protection Degree IP41

Under normal input conditions energy from the main circuits is channelled through the AC/DC converter. Surge and spikes will be blocked completely at the input converter and very instable supply shall be supported.

In normal condition the UPS shall be capable to operate in all the 125 or 110 VDC battery conditions (floating voltage, equalizing voltage and final discharge voltage)

In the events of main circuit failure the static switch will transfer the energy to through the transformer. The transfer time shall be not less than 2 ms.

After failure fixing the transfer to normal condition shall be done manually.

A manual by-pass switch shall permit the transfer from normal supply and vice versa for maintenance purpose.

b. Construction Characteristics

The AC/DC converter shall be of last generation type, possibly PWM (Pulse Width Modulation)

The ups shall house the following components:

? one DC/AC inverter;

? one emergency circuits composed by one transformer, reactors

? static switches;

? one manual bypass;

? distribution system.

The transformer shall be dry type with insulation class H and installed on anti-vibration support and placed in such a way to have easy accessibility.

Each output circuit shall be protected by a miniature circuit breaker.

On the front of the board at least the following signalizations shall be foreseen:

? Normal Supply;

? Emergency Supply

? Internal Failure;

? Low output voltage;

? High output voltage;

? Low input voltage;

? Earth fault

It shall be foreseen a communication port for the communication with PC.

注:1.交流屏具备交流失电后自启发电机功能;

2.直流电源系统应选用各个投标厂家的品牌或国内知名品牌,具备招标图纸上要求的功能(如交直流的电流、电压、开关量监控,绝缘监视,报警故障信号,电池巡检,可连接后台自动化系统等功能)

3.交直流系统,所有交流器件开关和ATS开关选用常熟开关制造有限公司(原常熟开关厂)品牌,所有直流器件开关选用北京人民电器厂;

4.按钮指示灯转换开关选用西门子APT或同等合资品牌(如施耐德/ABB);

5.根据标书技术规范要求,直流屏应选用指针表应选用96*96,广角度240°指针方向的指针表(如直流电压表,直流电流表,交流电压表,交流电流表等);交流屏使用数显表应选用96*96表,品牌长沙威盛或同等知名品牌(有英文报告和操作使用说明书的要求,便于报审);

6..电池品牌选用山东圣阳,深圳一电,河南新太行等国内知名品牌;

7.端子、连接件、字码选用菲尼克斯;

8.屏柜底部全部采用带黑皮封堵的防水格兰头PG型号,以便于进出线缆。

Shedule of Guaranteed Characteristics LOT 3A

Schedule of guaranteed characteristics

24.?? Batteries and chargers

Description

Requested

Guaranteed

A)? BATTERY 125 V, DC

- Manufacturer

- Type,

lead - acid

- Voltage per cell, D.C. (V)

2

- Capacity at 12-hr discharge rate (AH)

500

- Number of cells

64 (60+4 spare)

- Dimensions of each cell, (mm)

- Weight (kg)

- Standard applied

IEC 896, DIN

B)? BATTERY 48 V, DC

- Manufacturer

- Type

Lead Acid

- Voltage per cell, D.C. (V)

2

- Capacity at 8-hr discharge rate (AH)

250

- Number of cells

26 (24+2 spare)

- Dimensions of each cell, (mm)

- Weight (kg)

- Standard applied

IEC 896, DIN

C)? CHARGER FOR 125 V, DC BATTERY

- Manufacturer

- Type

- Current adjustment range (A)

0 - 200

- Maximum quick-charge current (A)

> 60

- Output (V, DC)

Float voltage:130V/ Boosting voltage:136V

- Regulation (%)

+ 0. 5

- Power frequency test voltage (kV)

2

- Dimensions (mm)

800*800*2260

- Standard applied

IEC 60146-1

D)? CHARGER FOR 48 V, DC BATTERY

- Manufacturer

- Type

- Current adjustment range (A)

0 - 150

- Maximum quick-charge current (A)

> 80

- Output (V, DC)

Float voltage :54v ;Boosting vlotage:56v

- Regulation (%)

+ 0. 5

- Power frequency test voltage (kV)

2

- Dimensions (mm)

800*800*2260

- Standard applied

IEC 60146-1

Schedule of guaranteed characteristics

25.??? A.C. DISTRIBUTION PANEL

Description

Requested

Tendered

- Manufacturer

- Place of manufacture

- Type

- Rated voltage, (V)

400V

- Rated current of main bus bar (A)

630

- Cross-section of bus bar (sq.mm)

TMY 60*5

- Permissible short circuit current (kA)

> 40

- Thickness of sheet steel, (mm)

2

- Applied test voltage, 50Hz 1 min (kV)

2.5

- Dimensions?

?? 1.? Length, (mm)

800

?? 2.? Width, (mm)

800

?? 3.? Height, (mm)

2260

- Weight (kg)

- Manufacturers catalogues designation of? A.C. panel and low voltage equipment

Attached

- Standards applied

IEC or equiv.

Schedule of guaranteed characteristics

26.??? D.C. DISTRIBUTION PANEL

Description

Requested

Tendered

- Manufacturer

- Type

- Place of manufacture

- Rated voltage, (V)

125, V, DC

- Cross-section of bus bar (sq.mm)

TMY 30*5

- Thickness of sheet steel, (mm)

2.5

- Permissible short circuit current (kA)

> 6

- Applied test voltage, 50Hz 1 min (kV)

2

- Dimensions?

?? 1.? Length, (mm)

800

?? 2.? Width, (mm)

600

?? 3.? Height, (mm)

2260

- Weight (kg)

- Manufacturers catalogues designation of? d.c. panel and low voltage equipment

Attached

- Standards applied

IEC or equiv.

Schedule of guaranteed characteristics

27.?? Uninterruptable power supply (UPS)

Description

Requested

Guaranteed

Manufacturer

Type / Model

Place of manufacture

a) Input DC

Maximum Input power

10KVA

DC Voltage Range, mpp

110 - 1000

Maximum DC voltage

1000 V

Maximum DC current

72.7A

Number of DC Inputs Pair

2

DC Connection Type

Copper wire

b) Output (AC)

Nominal Power

10kVA

AC Connection Type

1Ph, 2W=+PE

Maximum Output Power

10kVA

Power Factor

> 0.9

Nominal AC current

Nominal Single Phase Output Voltage

220 +/- 10% V

Output frequency

50Hz

Total Harmonic Distortion, Current

< 3%

Efficiency

> 95%

c) Power Consumption

Own consumption in operation

10% Own power
(Line mode)

Standby operation consumption

8%Standby operation power(BAT.mode)

External Auxiliary Voltage

230V, 50Hz

d) Environmental Limit

Degree of protection

IP42

Ambient temp. range (nom. ratings), deg celsius

15 - 50

Maximum ambient temperature, deg celsius

55

Maximum altitude (above sea level), meter

4000

Maximum noise level, dBA

75

e) Protections Type

Ground fault monitoring, Yes/No

Yes

DC Reverse Polarity, Yes/No

Yes

AC and DC short circuit and overcurrent, Yes/No

Yes

AC and DC over voltage and temperature,? Yes/No

Yes

AC Circuit Breaker, KA

20

f) User Interface & Communication

Local user interface

LCD

Fieldbus connectivity

Modbus/Ethernet

g) Dimension & Weight

??? * Size (L x W x H), mm

800 x 800 x 2260

??? * Weight

200

??? * Mounting Type

Floor Mounted

h) Standard Applied

IEC

Guaranteed Characterstics-LOT 4A

5.32) Schedule of guaranteed characteristics

Description

Requested

Guaranteed

- BATTERY 125 V, DC

a) Manufacturer

b) Type

lead - acid

c) Voltage per Cell, D.C. (V)

2

d) Capacity at 10-hr discharge rate (AH)

400

e) Number of cells

64 (60+4 spare)

f) Dimensions of each cell, (mm)

g) Weight (kg)

h) Standard applied

IEC 896, DIN

- CHARGER FOR 125 V, DC BATTERY

a) Manufacturer

b)Type

c) Current adjustment range (A)

0 - 80

d) Maximum quick-charge current (A)

> 60

e) Output (V, DC)

Float voltage:130v/ Boosting voltage:136v

f) Regulation (%)

+ 0. 5

g) Power frequency test voltage (kV)

2

h) Dimensions (mm)

800*800*2260

i) Standard applied

IEC 146-1

The Proposal technical data will be approved by the engineer during the approval stage after the manufacture offer completed

5.34)Schedule of guaranteed characteristics

Description

Requested

Guaranteed

- Manufacturer

- Type

- Place of manufacture

- Rated voltage, (V)

125, V, DC

- Cross-section of bus bar (sq.mm)

TMY 30*5

- Thickness of sheet steel, (mm)

2.5

- Permissible short circuit current (kA)

> 6

- Applied test voltage, 50Hz 1 min (kV)

2

- Dimensions?

?? 1.? Length, (mm)

800

?? 2.? Width, (mm)

800

?? 3.? Height, (mm)

2260

- Weight (kg)

250

- Manufacturers catalogues designation of? d.c. panel and low voltage equipment

Attached

- Standards applied

IEC or equiv.

The Proposal technical data will be approved by the engineer during the approval stage after the manufacture offer completed

5.35) Schedule of guaranteed characteristics

? A.C. DISTRIBUTION PANEL

Description

Requested

GUARANTEED

- Manufacturer

- Place of manufacture

- Type

- Rated voltage, (V)

400V

- Rated current of main bus bar (A)

800

- Cross-section of bus bar (sq.mm)

TMY 60*6

- Permissible short circuit current (kA)

> 20

- Thickness of sheet steel, (mm)

2

- Applied test voltage, 50Hz 1 min (kV)

2.5

- Dimensions?

?? 1.? Length, (mm)

800

?? 2.? Width, (mm)

800

?? 3.? Height, (mm)

2260

- Weight (kg)

250

- Manufacturers catalogues designation of? A.C. panel and low voltage equipment

Attached

- Standards applied

IEC or equiv.

5.36)? Schedule of guaranteed characteristics

? Uninterruptable Power Supply(UPS)

Description

Requested

Guaranteed

Manufacturer

Type / Model

Place of manufacture

a) Input DC

Maximum Input power

10KVA

DC Voltage Range, mpp

110 - 1000

Maximum DC voltage

1000 V

Maximum DC current

72.7

Number of DC Inputs Pair

2

DC Connection Type

Copper wire

b) Output (AC)

Nominal Power

10KVA

AC Connection Type

1Ph, 2W=+PE

Maximum Output Power

10kVA

Power Factor

> 0.9

Nominal AC current

Nominal Single Phase Output Voltage

220 +/- 10% V

Output frequency

50Hz

Total Harmonic Distortion, Current

< 3%

Efficiency

> 95%

c) Power Consumption

Own consumption in operation

10% Own power(Line mode)

Standby operation consumption

8%Standby operation power(BAT.mode)

External Auxiliary Voltage

230V, 50Hz

d) Environmental Limit

Degree of protection

IP42

Ambient temp. range (nom. ratings), deg celsius

15 - 50

Maximum ambient temperature, deg celsius

55

Maximum altitude (above sea level), meter

4000

Maximum noise level, dBA

75

e) Protections Type

Ground fault monitoring, Yes/No

Yes

DC Reverse Polarity, Yes/No

Yes

AC and DC short circuit and overcurrent, Yes/No

Yes

AC and DC over voltage and temperature,? Yes/No

Yes

AC Circuit Breaker, KA

20

f) User Interface & Communication

Local user interface

LCD

Fieldbus connectivity

Modbus/Ethernet

g) Dimension & Weight

??? * Size (L x W x H), mm

800 x 800 x 2260

??? * Weight

??? * Mounting Type

Floor Mounted

h) Standard Applied

IEC

5.38) Schedule of guaranteed characteristics

? Batteries and chargers For 48V

Description

Requested

Guaranteed

A)? BATTERY 48 V, DC

- Manufacturer

- Type

Lead Acid

- Voltage per cell, D.C. (V)

2

- Capacity at 8-hr discharge rate (AH)

250

- Number of cells

26 (24+2 spare)

- Dimensions of each cell, (mm)

- Weight (kg)

- Standard applied

IEC 896, DIN

B)? CHARGER FOR 48 V, DC BATTERY

- Manufacturer

- Type

- Current adjustment range (A)

0 - 150

- Maximum quick-charge current (A)

> 80

- Output (V, DC)

Float voltage :54v ;Boosting vlotage:56v

- Regulation (%)

+ 0. 5

- Power frequency test voltage (kV)

2

- Dimensions (mm)

800*800*2260

- Standard applied

IEC 60146-1

投诉异议 我要举报 18 [打印本页] [关闭]
返回顶部